How to choose the right check valve

In order to be able to choose the right check valve for your application there are a number of selection criteria you should consider. First of all, there is not one type of check valve being the best choice for all applications and different selection criteria may not be equally important for all cases.

Check valve types

Ball check valves

In general, ball check valves are simple and cost effective. Advantages are their compactness and the fact that they have no external parts which helps keeping the price low and the reliability high. A disadvantage may for some applications be that they do not have an open/close indicator. For more details, please visit the section about ball check valves.

Swing check valves

Swing check valves are the most common check valves. They are inexpensive and as they are automatic they do not require any external power or control to operate – only the flow direction determines the valve operation. Swing check valves with closed bushings do not have an open/close indicator but often the valves are mounted with lever and weight or lever and spring which enable visual check. For more details, please visit the section about swing check valves.

Tilting disc check valves

The tilting disc check valve is similar in appearance to an eccentric butterfly valve. The valve body is double‐flanged and of a short length. The disc is held in place via a shaft which is positioned eccentrically from the body centreline in both the horizontal and vertical axes.

The double eccentricity of the shaft results in the lower section of the disc occupying a greater area in the flow path. Consequently, the disc begins to open at very low flow rates. The tilting disc check valve is therefore commonly used in pumping systems with low flow rates and also for pulsating flows.

During flow reversal, the disc closes due to gravity and the upper part of the disc above the shaft centreline pushes against the flow thus acting as a hydraulic brake which cushions the disc as it returns to the closed position. Tilting disc valves can be supplied with optional levers and weights to adjust the closing characteristics of the valve. As such, the tilting disc check valves are well suited to reduce the risk of water hammers.

Because of the internal shafts which are within the flow stream, the tilting disc check valve is used for water and treated effluent applications. For more details, please see our tilting disc check valve product information.

Tilting disc, slanted seat check valves

The slanted seat check valve offers enhanced resistance to water hammer. The valve has the double eccentric shaft position as well as an increased seating angle. This yields a shorter valve stroke, thus reducing the time taken for the door to close. The slanted seat check valve can be installed with an optional hydraulic damper which is located at the internal base of the valve body.

Hydraulic dampers are recommended, especially when the valves are installed on a pumping station where high frequency opening and closing of the valve is required. Under these conditions, the damper will greatly protect the valve from accelerated wear and tear of the internal moving parts.

The slanted seat design also allows these valves to seal at lower back pressures. For more details, please see our slanted seat check valve product information.

Some of the selection criteria to consider when choosing your check valves

Some of the things you may need to consider are fluid compatibility, flow characteristics, headloss, non-slam characteristics and total cost of ownership. For optimal performance, it is of course important to choose your valve respecting the characteristics of each specific installation.

Fluid

All check valves are designed to handle water and treated wastewater but handling of raw waste water/sewage may cause some issues. When selecting a valve for these fluids, you should probably consider how the presence of solids may potentially affect operation of the valve.

Flow characteristics

If a check valve closes very fast, it may prevent slamming. However, the rapid closure will not protect against the surges caused by pumps being started and shut down. If the valve opens (and closes) quickly, the flow will be changed suddenly and surges will more likely occur.

Headloss

Headloss is a function of fluid velocity and the valve headloss is affected by the flow conditions of the system and the internal surface of the valve. The geometry of the valve body and the closure design determines the flow area through the valve and thereby also affects the headloss.

The headloss to be considered is a combination of static head (caused by elevation difference) and friction head (caused by the internal of the pipes and valves). There are a number of formulas for headloss and rating of valves based on this. The most common is probably the flow coefficient of the amount of water passing through the valve at a certain pressure drop during a certain amount of time. However, for comparisons the resistance coefficient Kv is considered the best choice.

Total cost of ownership

The costs for your check valve may consist of more than just the purchase price. For some installations, the most important costs may be purchasing and installation but in other cases maintenance or energy costs may be equally or even more important. When considering costs as a selection criteria for your check valve, the total costs over the life of the valve should therefore be considered. In general, the more simple the valve construction is, the lower are the maintenance requirements.

Non-slam characteristics

Check valve slam results in system pressure surge. First step of the process is when the pumps stop and the flow is reversed. That may cause some reverse flow through the valve before it gets to a fully closed position. Then the reverse flow is shut off and the change in flow velocity turns the kinetic energy of the fluid into pressure.

A slam sounds like if the disc or the ball from the check valve is hitting the seat and can make quite some noise. However, the sound is not caused by the physical closing but by a sound wave arising from a pressure spike stretching the pipe wall. To completely avoid slamming, the check valve should close before any reverse velocity can occur. Unfortunately, that does not happen. The geometry of the valve decides how much reverse flow will occur so the faster the valve closes, the less slamming.

As swing check valves have the disc in the flow stream helping with rapid closure, they have better non-slam characteristics but today most pumps are frequency converted enabling them to adjust the start-up and closure time in order to avoid water hammer.

Check valves can be installed both horizontally and vertically. Slamming may be a bigger issue for vertical installations since a vertical flow reverses more rapidly but a vertical installation allows gravity to assist in closing the valve rapidly.

Case

Building a brand new neighbourhood

BudaPart is a brand new neighbourhood in Budapest with residential buildings, office buildings and services. A total of 600,000 square metres will be built and for the first part of the project, we have delivered two pcs. DN500 tilting disc check valves and six pcs. DN500 dismantling joints.

Brochure

Water supply

Get a complete overview of our valves, hydrants and accessories for water supply including full information about their features and benefits
Our website uses cookies for statistical analysis, to improve our website and serve you optimally. By visiting our website, you consent to our and third party use of cookies as described in our privacy and cookie policy.
Read more