AVK GATE VALVE, FLANGED/PE PIPE END, PN16

Black/blue SDR11 PE100 pipe end, DN50-200

AVK headquater in Skovby Galten, Denmark

Contact

AVK International A/S

Bizonvej 1, Skovby, 8464 Galten, Denmark

Gate valve with flange/PE100 PN16 SDR11 pipe end. For water and neutral liquids to max. 20° C. Note: The maximum working temperature is set according to the ISO9080 lifetime requirements for PE pipes, and is therefore not the max. temperature for the valve.

AVK gate valves are designed with built-in safety in every detail. The wedge is fully vulcanized with AVK’s own drinking water approved EPDM rubber compound. It features an outstanding durability due to the ability of the rubber to regain its original shape, the double bonding vulcanization process and the sturdy wedge design. The triple safety stem sealing system, the high strength stem and the thorough corrosion protection safeguard the unmatched reliability.

Variant 38/80-116
Connection: Flange x PE Pipe End
Material: Ductile Iron
DN: DN50 - DN200
PN: PN16
Closing direction: Clockwise to close

Features

  • Fixed, integral wedge nut prevents vibration and ensures durability
  • Wedge fully vulcanized with drinking water approved EPDM rubber and equipped with wedge shoes to provide smooth operation
  • Large conical stem hole in the wedge prevents stagnant water
  • Wedge and body guide rails ensure stable operation
  • Stainless steel stem with wedge stop and rolled threads for high strength
  • Full circle thrust collar provides fixation of the stem and low free running torques
  • Triple safety stem sealing with an NBR wiper ring, a polyamide bearing with four NBR O-rings and an EPDM rubber manchette
  • Round EPDM bonnet gasket fixed in a recess
  • Countersunk and sealed stainless steel bonnet bolts encircled by the bonnet gasket
  • Full bore
  • Low operating torque
  • Fusion bonded epoxy coating in compliance with DIN 3476 part 1 and EN 14901, GSK approved
  • A standard PE pipe is pressed onto the grooved valve end, locked with a steel ring and sealed with a plastic shrink hose. The boltless, full bore PE end connection is tensile resistant and stronger than the PE pipe itself. The PE pipe end enables direct welding into PE pipes resulting in a fast and secure assembly.
    Note: The maximum working temperature of 20°C is set according to the ISO9080 lifetime requirements for PE pipes. For higher working temperatures expect a reduction of the PE pipe’s lifetime. Please refer to the local pipe manufacturer for further information.

Downloads

Datasheet
Appendix
Installation
Certificate(s)

Reference nos. and dimensions:

Scroll for more info
AVK ref. no. DN
mm
D
mm
Flange
drilling
H
mm
H3
mm
L
mm
L1
mm
F
mm
F1
mm
F2
mm
Theoretical
weight/kg
38-063-80-163 50 63 PN10/16 241 324 565 125 14 17 29 11
38-075-80-163 65 75 PN10/16 271 364 596 135 17 20 34 16
38-090-80-16306499 80 90 PN10/16 282 382 543 100 17 20 34 13
38-110-80-16306499 100 110 PN10/16 305 415 544 106 19 22 34 17
38-125-80-16306499 125 125 PN10/16 346 471 547 110 19 22 34 23
38-160-80-16306499 150 160 PN10/16 400 543 643 110 19 22 34 35
38-180-80-16306499 150 180 PN10/16 400 543 647 118 19 22 34 35
38-200-80-16306499 200 200 PN10 400 543 647 132 24 27 34 61
38-225-80-16306499 200 225 PN10 490 660 671 132 24 27 34 63
BIM drawings
2D/3D drawings
Enquiry
Scroll for more info

Components

1. Stem Stainless steel 1.4104 (430F)
2. Wiper ring NBR rubber
3. O-ring NBR rubber
4. Bearing Polyamide
5. Bonnet Ductile iron GJS-400-15 (GGG-40)
6. Thrust collar Brass, DZR CW602N
7. Manchette EPDM rubber
8. Bonnet bolt Stainless steel A2, sealed with hot melt
9. Bonnet gasket EPDM rubber
10. Wedge nut Brass, DZR CW626N
11. Wedge Ductile iron, EPDM encapsulated
12. Body Ductile iron GJS-400-15 (GGG-40)
13. Sleeve Carbon steel
14. Shrink hose Plastic
15. Pipe PE

Test/Approvals

  • Seat: 1.1 x PN (in bar), Body: 1.5 x PN (in bar). Operation torque test
  • Approved according to SVGW Certificate No. 0301-4608 for pipe Ø ≤ 400mm
  • Belgaqua approved
  • Approved according to ACS Certificate 18 ACC NY 369

Standards

  • Designed according to EN 1074 part 1 & 2, Designed according to EN 1171
  • Standard flange drilling to EN1092-2 (ISO 7005-2), PN10/16
0 Files In the package