AVK ABOVE-GROUND FIRE HYDRANT, PN16

Model P7 "Nostalgia" Type C with additional ball shut-off, 2 x B + 1 x A, DN100

AVK headquater in Skovby Galten, Denmark

Contact

AVK International A/S

Bizonvej 1, Skovby, 8464 Galten, Denmark

Above-ground fire hydrant model P7 "Nostalgia" with 2 x hose storz B / 1 x pumper nozzle A outlet for drinking water and neutral liquids to max. 60° C

AVK series 84 above-ground hydrants have many safety features and meet or exceed the requirements of DIN EN 14384. The hydrant is designed with double shut-off system for a continued sealing of the hydrant during maintenance and in the case of an accidental traffic knock down. The flanges connecting the upper and the lower barrel are assembled with special titanium bushes designed to break if something is hitting the hydrant. These bushes are the only spare parts to be replaced in case of a breakdown.

fire
fire
Variant 84/51-003
Material: Ductile Iron
DN: DN100 - DN100
PN: PN16
Closing direction: Clockwise to Close

Features

  • 2 x B storz hose nozzles, 1 x A storz pumper nozzle
  • Valve seat of dezincification resistant brass
  • Fully vulcanized ball sealing gasket
  • Automatic drainage in flush proof design
  • Operating nut with integrated air valve of brass
  • Disc with ductile iron core coated with PUR (Polyurethan) for maximum memory effect
  • Titanium bushes in the upper barrel flange, protecting against damage at traffic knock down
  • Additional ball shut-off for easy maintenance of the hydrant
  • Kv value: 1 x 65 outlet: 209 m³/h, 2 x 65 outlet: 234 m³/h, 1 x 100: 256 m³/h
  • Drainage: Residual flow: 22 ml.
  • Time for drainage: 206 sec.
  • Operating force resistance: MOT = 125 Nm, MST = 250 Nm
  • Fusion bonded epoxy coating to DIN 3476 part 1 and EN 14901 externally, enamel to DEV internally and with a topcoat of UV resistant polyester. Optionally top + bottom externally enamelled red or blue to DIN 51178
  • The gear positioned in the lower part and a loosely plugged connection of the operation pipes, makes the main hydrant sealing remain fully functional at an accidental traffic knock down
  • Possibility of rotation of the upper barrel including the hydrant head by 360°

 

Downloads

Datasheet
Certificate(s)

Reference nos. and dimensions:

Scroll for more info
AVK ref. no. DN
mm
Pipe cover
mm
H3
mm
H8
mm
H9
mm
Theoretical
weight/kg
Notes
84-100-51-211011 100 1000 1865 725 265 93
84-100-51-211062 100 1000 1865 725 265 93 Hydrant body red enamelled outside
84-100-51-311011 100 1250 2115 975 265 98
84-100-51-311062 100 1250 2115 975 265 98 Hydrant body red enamelled outside
84-100-51-411062 100 1500 2365 1225 265 105 Hydrant body red enamelled outside
Enquiry
Scroll for more info

Components

1. Ball chamber Ductile iron GJS-400-15 (GGG-40)
2. Ball PP
3. Main seal ring Ductile iron, EPDM encapsulated
4. Locking segment HDPE
5. Washer Stainless steel A2
6. Bolt Stainless steel A2
7. Seat Brass
8. Operation pipe Stainless steel 1.4021, GJS (GGG), PUR
9. Stem nut Brass
10. Hydrant body, lower Ductile iron GJS-400-15 (GGG-40)
11. Washer POM
12. Lower stem Stainless steel 1.4021
13. Stem guide Ductile iron GJS-400-15 (GGG-40)
14. Helical roll pin Stainless spring steel 1.4310
15. Ring Ductile iron GJS-400-15 (GGG-40)
16. Bolt, socket head Stainless steel A2
17. Clamp half Ductile iron GJS-400-15 (GGG-40)
18. O-ring EPDM rubber
19. Bushing Titanium
20. Blocking ring Ductile iron GJS-400-15 (GGG-40)
21. Operation pipe top Stainless steel 1.4021, GJL (GG)
22. Hydrant body, top Ductile iron GJS-400-15 (GGG-40)
23. O-ring EPDM rubber
24. Cover B Aluminium
25. Coupling B Aluminium
26. O-ring EPDM rubber
27. Bearing bush Brass
28. Wiper ring NBR rubber
29. Washer Polyamide
30. Hexagon head Aluminium
31. Helical roll pin Stainless spring steel 1.4310
32. Drain pipe PA, POM
33. Air valve Brass

Test/Approvals

  • Hydraulic test according to EN 1074-6 / W 386-P, Hydraulic test according to EN 1074-1 and 2 / EN 12266
  • Approved according to CE Reg. No. 0620-CPR-6122
  • Approved according to DIN-DVGW Certificate NW-6411CO0337

Standards

  • Designed according to EN 1074 - 6:2008, Design according to EN 14384:2005
  • Standard flange drilling to EN1092-2 (ISO 7005-2), PN16
0 Files In the package